SPECIFICATIONS
Technical specifications
| Parameter | Unit | GSSG-500B | GSSG-1000B |
|---|---|---|---|
| Steam capacity | kg/h | 500 | 1000 |
| Steam pressure | MPa | 0.8 | 0.8 |
| Thermal efficiency | % | 101 | 101 |
| NOx emission | mg/Nm³ | < 20 | < 20 |
| Combustion control | 20 – 100% proportional | ||
| Water capacity | L | < 50 | < 50 |
| Steam outlet | DN | 40 | 50 |
| Safety valve | DN | 32 × 2 | 40 × 2 |
| Water inlet | DN | 25 | 25 |
| Gas valve bank | DN | 40 | 50 |
| Drain outlet | DN | 40 | 40 |
| Condenser tube | DN | 15 | 25 |
| Exhaust diameter | mm | 160 | 200 |
| Natural gas | Nm³/h | 38 | 75 |
| LPG | kg/h | 29.7 | 58 |
| Rated power | kW | < 4 | < 5 |
| Power supply | 380V / 50Hz | ||
| Dimensions (L×W×H) | mm | 1800×1100×2000 | 1950×1270×1980 |
| Weight | kg | 850 | 1350 |
GSSG-500B
- Steam capacity (kg/h)
- 500
- Steam pressure (MPa)
- 0.8
- Thermal efficiency (%)
- 101
- NOx emission (mg/Nm³)
- < 20
- Combustion control
- 20 – 100% proportional
- Water capacity (L)
- < 50
- Steam outlet (DN)
- 40
- Safety valve (DN)
- 32 × 2
- Water inlet (DN)
- 25
- Gas valve bank (DN)
- 40
- Drain outlet (DN)
- 40
- Condenser tube (DN)
- 15
- Exhaust diameter (mm)
- 160
- Natural gas (Nm³/h)
- 38
- LPG (kg/h)
- 29.7
- Rated power (kW)
- < 4
- Power supply
- 380V / 50Hz
- Dimensions (L×W×H) (mm)
- 1800×1100×2000
- Weight (kg)
- 850
GSSG-1000B
- Steam capacity (kg/h)
- 1000
- Steam pressure (MPa)
- 0.8
- Thermal efficiency (%)
- 101
- NOx emission (mg/Nm³)
- < 20
- Combustion control
- 20 – 100% proportional
- Water capacity (L)
- < 50
- Steam outlet (DN)
- 50
- Safety valve (DN)
- 40 × 2
- Water inlet (DN)
- 25
- Gas valve bank (DN)
- 50
- Drain outlet (DN)
- 40
- Condenser tube (DN)
- 25
- Exhaust diameter (mm)
- 200
- Natural gas (Nm³/h)
- 75
- LPG (kg/h)
- 58
- Rated power (kW)
- < 5
- Power supply
- 380V / 50Hz
- Dimensions (L×W×H) (mm)
- 1950×1270×1980
- Weight (kg)
- 1350
Boiler: composite boiler steel + 316 stainless fins · Condenser: 316 stainless steel
Protection: low-water, over-temperature, over-pressure, high-flue-temp, low-gas-pressure & mechanical E-stop
Data for reference only. Refer to the unit nameplate for binding specifications.
FAQ
Frequently asked questions
BRAVO is a fully condensing, ultra-low-NOx gas steam generator from GreenSeed®. It comes in 500 kg/h (GSSG-500B) and 1000 kg/h (GSSG-1000B) models and reaches up to 101% thermal efficiency.
The figure is based on the fuel’s net calorific value. The GreenSeed® BRAVO’s condenser cools flue gas below 60 °C and recovers latent heat from water vapour that conventional boilers lose up the chimney, so measured efficiency can exceed 100% on a net basis.
Recovering flue-gas heat can cut fuel use by up to about 12% compared with a conventional gas boiler, which lowers both bills and emissions.
No. BRAVO is delivered as a compact, pre-tested whole unit and can be installed where steam is needed. That reduces infrastructure costs.
Yes. BRAVO is the first steam generator of its kind in Malaysia approved by JKKP (DOSH) and is CE certified. As with any steam boiler in Malaysia, installation needs DOSH registration and a Certificate of Fitness.
Natural gas or LPG. The GSSG-500B uses 38 Nm³/h of natural gas or 29.7 kg/h of LPG; the GSSG-1000B uses 75 Nm³/h or 58 kg/h.
Below 20 mg/Nm³, thanks to premix combustion.